Details
The vibration and shock resistance can only be met if the cables are fixed at an appropriate distance. Instructions for the spacing of strain relief can be found in the document in eCatalogue under the section Instructions.
Technical characteristics
Conductor cross-section
35 ... 70 mm²
Wire outer diameter
≤19.5 mm
Rated current
350 A
Rated voltage
2,000 V
Rated impulse voltage
12 kV
Pollution degree
3
Insulation resistance
>1010 Ω
Contact resistance
≤ 0,2 mΩ
Stripping length
19 ... 20 mm
Tightening torque
8 Nm @ 35 mm²
10 Nm @ 50 mm²
12 Nm @ 70 mm²
Limiting temperature
-40 ... +125 °C
Mating cycles
≥ 500
Vibration resistance
Category 2 acc. to IEC 61373
Shock resistance
Category 2 acc. to IEC 61373
Material properties
Material (insert)
Polikarbonát (PC)
Poliamid (PA)
Colour (insert)
RAL 7032 (kavicsszürke)
Material (contacts)
Réz ötvözet
Surface (contacts)
Ezüst bevonatú
Material flammability class acc. to UL 94
V-0
RoHS
konform, kivétellel
RoHS exemptions
6. a) / 6. a) I.: Ólom a megmunkálásra szánt acél ötvözőelemeként, illetve galvanizált acélban, legfeljebb 0,35 tömegszázalék ólomtartalomig / Ólom a megmunkálásra szánt acél ötvözőelemeként, legfeljebb 0,35 tömegszázalék ólomtartalomig, illetve a szakaszosan tűzihorganyzott acélban, legfeljebb 0,2 tömegszázalék ólomtartalomig
6. c): Rézötvözet legfeljebb 4 tömegszázalék ólomtartalommal