The described connectors are connectors without breaking capacity (COC) according to IEC 61984 and must not be coupled or decoupled under electrical load during use as intended!
Only cables with protection class 2 shall be used!
The axial screw termination is suitable for fine stranded wires according to EN 60228 class 5. Using alternative cables have to be tested separately.
For the assembly within bulkhead mounted housings the described installation conditions of the data and type sheets must be respected.
Only the housings linked in the eShop shall be used!
For the connection of the conductor into the axial screw contact use hex key with AF 4.
Technical characteristics
Conductor cross-section
16 ... 25 mm²
Conductor cross-section [AWG]
AWG 6 ... AWG 4
Rated current
100 A
Rated voltage
400 V
Rated impulse voltage
6 kV
Pollution degree
3
Insulation resistance
>1010 Ω
Contact resistance
≤ 0.3 mΩ
Stripping length
10 mm
Tightening torque
6 ... 7 Nm
Limiting temperature
-40 ... +125 °C
Mating cycles
≥ 500
Material properties
Material (insert)
Polycarbonate (PC)
Polyamide (PA)
Colour (insert)
RAL 7032 (pebble grey)
Material (contacts)
Copper alloy
Surface (contacts)
Silver plated
Material flammability class acc. to UL 94
V-0
RoHS
compliant with exemption
RoHS exemptions
6(c): Copper alloy containing up to 4 % lead by weight