Details
The vibration and shock resistance can only be met if the cables are fixed at an appropriate distance. Instructions for the spacing of strain relief can be found in the document in eCatalogue under the section Instructions.
Technical characteristics
Conductor cross-section
150 mm²
Rated current
≤ 650 A
Contact resistance
≤ 0.3 mΩ
Stripping length
42 mm
Limiting temperature
-40 ... +125 °C
Mating cycles
≥ 500
Vibration resistance
Category 1B acc. to IEC 61373
Shock resistance
Category 1B acc. to IEC 61373
Material properties
Material (contacts)
Alliage de cuivre
Surface (contacts)
Plaqué argent
RoHS
conformité avec exemption
RoHS exemptions
6 c): L'alliage de cuivre contenant jusqu'à 4 % de plomb en poids
ELV status
conformité avec exemption
China RoHS
50
REACH Annex XVII substances
Non contenu
REACH ANNEX XIV substances
Non contenu
REACH SVHC substances
Oui
REACH SVHC substances
Plomb
ECHA SCIP number
b51e5b97-eeb5-438b-8538-f1771d43c17d