The vibration and shock resistance can only be met if the cables are fixed at an appropriate distance. Instructions for the spacing of strain relief can be found in the document in eCatalogue under the section Instructions.
Technical characteristics
Conductor cross-section
35 ... 70 mm²
Wire outer diameter
≤19.5 mm
Rated current
350 A
Rated voltage
2,000 V
Rated impulse voltage
12 kV
Pollution degree
3
Insulation resistance
>1010 Ω
Contact resistance
≤ 0,2 mΩ
Stripping length
19 ... 20 mm
Tightening torque
8 Nm @ 35 mm²
10 Nm @ 50 mm²
12 Nm @ 70 mm²
Limiting temperature
-40 ... +125 °C
Mating cycles
≥ 500
Vibration resistance
Category 2 acc. to IEC 61373
Shock resistance
Category 2 acc. to IEC 61373
Material properties
Material (insert)
Polikarbonat (PC)
Poliamid (PA)
Colour (insert)
RAL 7032 (çakıl grisi)
Material (contacts)
Bakır alaşımı
Surface (contacts)
Gümüş kaplı
Material flammability class acc. to UL 94
V-0
RoHS
muafiyete uygun
RoHS exemptions
6(a) / 6(a)-I: Talaşlı imalat amaçlı çelikte ve ağırlıkça %0,35'e kadar kurşun içeren galvanize çelikte alaşım elemanı olarak kurşun / Talaşlı imalat amaçlı çelikte alaşım elemanı olarak kurşun ağırlıkça %0,35 kurşun ve yığın halinde ağırlıkça %0,2'ye kadar kurşun içeren sıcak daldırma galvanize çelik bileşenler
6(c): Ağırlıkça %4'e kadar kurşun içeren bakır alaşımı